Battery inverter SMA Sunny Central Storage 2400 UP-XT
Sunny Central Storage UP-XT
Extended mains power
Battery inverter for large scale systems
With max. With output power up to 3067 kVA and system voltage up to 1500 VDC, SMA Sunny Central Storage enables more efficient and flexible system design for battery power plants.
SCS UP-XT versions allow systems with higher output power and higher short circuit current. The intelligent OptiCool cooling system ensures smooth operation even in extreme ambient temperatures.
Effective
• Up to 4 inverters can be transported in one standard shipping container.
• Higher power density
• Higher power in the mains supply direction
• Higher short circuit contribution
Strong
• Intelligent OptiCool air cooling system for efficient cooling.
• Suitable for outdoor use in all climates according to to the whole world.
Flexible
• One device for all applications
• Stand-alone device or complete solution with medium voltage SMA system.
Universal
• Built-in battery communication
• Individual monitoring and control of inverters.
• Network management functions to support dynamic networking.
• Built-in voltage source for internal consumption and external loads.
Technical data SCS 2400 UP-XT
Battery side (DC)
DC operating voltage range VDC: 921V to 1500V.
Max. Direct current I DC, max.: 3200 A
Battery Connection Fuse Specification - Integral Pre-Arc Limit, Single DC Bus /
split DC bus 12) 15): 10.75 MA²s / 8.0 MA²s
Single DC bus, 36 connections per pole / split DC bus, 6/5 connections per pole: ● / ○
DC connection: with terminal lug
AC side
Nominal AC discharge power at 1200 V DC and cos φ =1.0 (at 25°C): 2800 kW
Mains mode: AC full power at 1200 VDC (at 25°C / at 40°C / at 50°C) 3) 13) 14): 2800 kVA / 2548 kVA / 2380 kVA
Charging mode: Full AC power at 1200 VDC (at 25°C / at 40°C / at 50°C) 3) 13) 14): 2513 kVA / 2288 kVA / 2101 kVA
Max. Alternating current IAC, no more (at 25°C/at 40°C/at 50°C): 2566 A/2335 A/2181 A
Max. total harmonic distortion: <3% at rated power
Rated AC voltage / AC voltage range 1) 8): 630 V / 504 V to 756 V
AC Frequency/Range: 50Hz/47-53Hz
60 Hz / 57 Hz to 63 Hz
Min. AC terminal short circuit factor 9): > 2
Cos Phi at rated power/displacement Cos Phi adjustable 8) 10): from 1 / 0.0 for overexcitation to 0.0 for underexcitation
AC connection: with bus system (three buses, one for each line wire)
Efficiency
Max. efficiency 2): 98.7%
Protective devices
Input side disconnect point: DC load breaker
Output side disconnect point: AC circuit breaker
DC surge protection: Type I surge suppressor.
AC surge protection (optional): Surge suppressor, class I.
Lightning protection (according to IEC 62305-1): Lightning protection level III
Insulation monitoring: ●
Degree of protection: electronics/ducting/connection area (according to IEC 60529): IP54/IP34/IP34
Total information
Dimensions (W/H/D): 2815/2318/1588 mm
Weight: < 3400 kg
Self-consumption (max.4) / part load 5) / average 6)): < 8100 W / < 1800 W / < 2000 W
Self-consumption (standby): < 370 W
Internal (8.4 kVA transformer)/external auxiliary power supply: ● / ○
Noise level 7): 63.0 dB(A)
Operating temperature range (optional) 8): (-40°C) -25°C to 60°C
Range Temperature (standby): −40°C to 60°C.
Temperature range (storage): −40°C to 70°C.
Max. permissible relative humidity (with/without condensation): 95% to 100% (2 months/year) / 0% to 95%
Maximum operating altitude 8) 1000 m / 2000 m 11): ● / ○
Fresh air flow: 6500 m³/h
Functions
Mesh formation/black start ready: ○ / ○
Communication: Ethernet, Modbus Master, Modbus Slave
Communication with SMA Line Monitor (Transmission Media): Modbus TCP/Ethernet (FO MM, Cat-5)
Body/ceiling colour: RAL 9016/RAL 7004
Supply transformer for external loads: ○ (2.5 kVA)
Complies with standards and directives: CE, IEC/EN 62109-1/-2, AR-N 4110/4120, Arrêté du 23/04/08.
EMC Standards: IEC 61000-6-2, EN 55011, CISPR11, FCC Part 15 Class A.
Complies with quality standards and directives: VDI/VDE 2862 page 2, DIN EN ISO 9001.
Type designation SCS 2400 UP-XT
● Standard Features ○ Advanced —Not available.
1) Below rated voltage AC power is reduced in the same proportion.
2) Efficiency measured without internal power supply.
3) Full AC power at higher DC voltages on request.
4) Own consumption at nominal operation
5) Self-consumption at < 75% Pn at 25°C
6) Self-consumption averages from 5% to 100% Pn at 25°C.
7) Sound pressure level at a distance of 10 m.
8) Values only apply to inverters. The permissible values for SMA MV solutions from SMA can be found in the corresponding data sheets.
9) Short circuit ratio < 2 requires special SMA approval.
10) Max. Power values (S/P/Q) may be requested depending on the specific project.
11) Earlier temperature derating and DC open circuit voltage reduction.
12) Disconnecting the battery from short circuit should be done on the battery side using ultra-fast battery pack or group fuses, e.g. fuse type aR/aBat and DC time constant Tau (L/R) <= 1 ms
13) These services can be provided on a long-term basis. Depending on the ambient temperature and the inverter temperature, the maximum temperature-dependent AC power can also be obtained in a short time.
14) Depending on the reactive power ratio (cos φ), extended power reduction may occur.
15) Please check the manual for more information.