Hybrid inverter Victron Energy MultiPlus 12/2000/80-32 VE.Bus (2 kVA/1.6 kW, 1 phase, without MPPT)
Multifunctional sinusoidal inverter with a maximum output power of 2000 W. and with a battery voltage of 12 volts.
Uninterruptible Power Supply Device for AC Power
In the event of a malfunction in the electrical network or when power is cut off from the generator or AC network, the MultiPlus 12/2000/80-32 inverter will automatically turn on and “seize” the power from the connected loads. This happens so quickly (less than 20 milliseconds) that gas boilers and heating systems continue to operate without interruption.
Main characteristics
Power control/power amplifier: Yes
Three-phase and parallel operation: Yes
Transfer switch: 35 A
INVERTER
Input voltage range: 9.5-17V 19-33V 38-66V
Exit:
Output voltage: 230 VAC ± 2% Frequency: 50 Hz ± 0.1% (1)
Continued output power at 25°C(3): 2000 VA
Continued output power at 25°C: 1600 W
Continued output power at 40°C: 1400 W
Continued output power at 65°C: 1000 W
Peak power: 3500 W
Maximum efficiency: 93/94/95%
No load power: 10/9/10 W
Power at no load in search mode: 3/3/3 W
CHARGER
AC input:
Input voltage range: 187-265 VAC. Input frequency: 45-65 Hz.
Charge voltage "absorption": 14.4/28.8/57.6 V
Floating charge voltage: 13.8/27.6/55.2 V
Storage mode: 13.2/26.4/52.8V
Home battery charge current: 80/50/25 A
Starter battery charging current: 1 A (12 V and 24 V models only)
Battery temperature sensor: Yes
GENERAL
Programmable Relay: Yes
Defense: a – d
VE.Bus communication port: for parallel and three-phase operation, remote monitoring and system integration.
(RJ45 splitter ASS030065510 is required for 500/800/1200 VA models)
Remote on-off: on/off
General characteristics:
Working temperature. range: -40 to +65°C (fan cooling) Humidity (non-condensing): max. 95 %
FRAME
General characteristics:
Material and color: Steel/ABS plastic (blue RAL 5012). Degree of protection: IP 21.
Battery connection: M8 bolts
Weight: 15.5 kg
Dimensions (H x W x D): 506 x 236 x 147 mm.
STANDARDS
Safety: EN-IEC 60335-1, EN-IEC 60335-2-29, EN 62109-1.
Radiation immunity: EN 55014-1, EN 55014-2, EN-IEC 61000-3-2, EN-IEC 61000-3-3, IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6 - 3
Automotive Directive: ECE R10-5
Protection:
A. Output short circuit
b. Overload
V. Battery voltage is too high
d. Battery voltage is too low
e. Temperature too high
and. 230 VAC inverter output
d. Input voltage ripple is too high